CVE-2020-25178
Description
ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files.
Related CPE's
References
CvssV3 impact
Version | 3.1 |
VectorString | CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H |
AttackVector | NETWORK |
AttackComplexity | LOW |
PrivilegesRequired | NONE |
UserInteraction | REQUIRED |
Scope | UNCHANGED |
ConfidentialityImpact | HIGH |
IntegrityImpact | HIGH |
AvailabilityImpact | HIGH |
BaseScore | 8.8 |
BaseSeverity | HIGH |
CvssV2 impact
Version | 2.0 |
VectorString | AV:N/AC:M/Au:N/C:C/I:C/A:C |
AccessVector | NETWORK |
AccessComplexity | MEDIUM |
Authentication | NONE |
ConfidentialityImpact | COMPLETE |
IntegrityImpact | COMPLETE |
AvailabilityImpact | COMPLETE |
BaseScore | 9.3 |