CVE-2020-25180
Description
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device.
Related CPE's
References
CvssV3 impact
Version | 3.1 |
VectorString | CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N |
AttackVector | NETWORK |
AttackComplexity | LOW |
PrivilegesRequired | NONE |
UserInteraction | REQUIRED |
Scope | UNCHANGED |
ConfidentialityImpact | HIGH |
IntegrityImpact | NONE |
AvailabilityImpact | NONE |
BaseScore | 6.5 |
BaseSeverity | MEDIUM |
CvssV2 impact
Version | 2.0 |
VectorString | AV:N/AC:M/Au:N/C:P/I:N/A:N |
AccessVector | NETWORK |
AccessComplexity | MEDIUM |
Authentication | NONE |
ConfidentialityImpact | PARTIAL |
IntegrityImpact | NONE |
AvailabilityImpact | NONE |
BaseScore | 4.3 |