Description


The firmware upgrade function in the admin web interface of the Rittal IoT Interface & CMC III Processing Unit devices checks if the patch files are signed before executing the containing run.sh script. The signing process is kind of an HMAC with a long string as key which is hard-coded in the firmware and is freely available for download. This allows crafting malicious "signed" .patch files in order to compromise the device and execute arbitrary code.

Related CPE's


Could not find any relations

Weaknesses


551230f0-3615-47bd-b7cc-93e92e730bbf

Secondary

CWE-347

CVSS impact metrics


CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

9.8 · Critical

Information


Source identifier

551230f0-3615-47bd-b7cc-93e92e730bbf

Vulnerability status

Awaiting analysis

Published

2024-10-15T07:15:03.357Z

1 year ago

Last modified

2025-11-03T22:16:23.247Z

5 months ago