Description


Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations (such as project/logic uploads and downloads). This password is set using the OMRON FINS command Program Area Protect and unset using the command Program Area Protect Clear, both of which are transmitted in cleartext.

References


https://www.cisa.gov/uscert/ics/advisories/icsa-22-179-02

Third Party AdvisoryUS Government Resource

Weaknesses



CWE-319

CVSS impact metrics


CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

7.5 · High

  • CVSS V3.1

  • CVSS V3.0

  • CVSS V2.0

Information


Source identifier

[email protected]

Vulnerability status

Analyzed

Published

2022-07-26T22:15:11.317

2 years ago

Last modified

2022-08-04T14:59:59.737